Distributed Power ModuleMODEL 5495Installation andOperations ManualDocument 15116108/12/13 Rev M151161:M ECN 13-0708

Seite 2

Model 5495 Distributed Power Module Installation Manual6 151161You can select which input controls which output, and which inputs are Class A and Clas

Seite 3 - Contents

Installation151161 7Section 4InstallationBefore installing the 5495, the AC input must first be wired into the building’s main electrical power throug

Seite 4

Model 5495 Distributed Power Module Installation Manual8 1511614.2 Wire RoutingTo avoid induced noise (transfer of electrical energy from one wire to

Seite 5 - Introduction

Installation151161 94.3 Current Requirements (Standby and Alarm)4.3.1 Current Drawn From Host Panel Table 4-1 shows the 5495 current draw requirements

Seite 6 - UL Requirements

Model 5495 Distributed Power Module Installation Manual10 151161Table 4-2: Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStand

Seite 7 - System Overview

Installation151161 114.4 Connecting the 5495 to a Control PanelFigure 4-2 shows the general layout of the 5495 PC board. This section also provides sp

Seite 8 - 3.2 Signal Input Terminals

Model 5495 Distributed Power Module Installation Manual12 1511614.4.1 Common Trouble Relay The 5495 has a Form C trouble relay built into Terminals 11

Seite 9 - 151161 5

Installation151161 134.5 Notification Appliance WiringNote:Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device

Seite 10 - DIP switch settings

Model 5495 Distributed Power Module Installation Manual14 151161pass the added current load from notification appliances.Figure 4-4 Class A Supervise

Seite 11 - Installation

Installation151161 15Class B Supervised Input CircuitsFigure 4-5 shows Class B supervised wiring from a fire alarm control panel to the 5495.Use an EO

Seite 13 - 151161 9

Model 5495 Distributed Power Module Installation Manual16 1511614.7 Battery ConnectionUse two 12 VDC, 7 AH gel cell batteries inside the 5495 cabinet.

Seite 14

Installation151161 174.8 DIP Switch SettingsA 7-position DIP switch on the 5495 board allows you to select the following:• How long the 5495 will wait

Seite 15 - 151161 11

Model 5495 Distributed Power Module Installation Manual18 1511614.8.1 Selecting the Standard Input/Output ConfigurationsFigure 4-7 and Figure 4-8 show

Seite 16 - 4.4.1 Common Trouble Relay

Installation151161 194.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded OutputsThe DIP switch settings marked with an asterisk (*) in

Seite 17 - 151161 13

Model 5495 Distributed Power Module Installation Manual20 1511614.8.2 Selecting Synchronized Output ConfigurationsThe following sections describe how

Seite 18 - 14 151161

Installation151161 214.8.2.3 Selecting Synchronized System Sensor ConfigurationsTo select the input/outputs for System Sensor synchronized appliances,

Seite 19 - 151161 15

Model 5495 Distributed Power Module Installation Manual22 1511614.8.3 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 3 hours

Seite 20 - 4.7 Battery Connection

Sample Applications151161 23Section 5Sample ApplicationsThe drawings in this section show various 5495 configurations, including “daisy-chaining”.5.1

Seite 21 - 4.8 DIP Switch Settings

Model 5495 Distributed Power Module Installation Manual24 151161Note:When multiple power supplies are used with one control unit they will not sync wi

Seite 22

Sample Applications151161 25Figure 5-5 Each Control NAC Activates Five Output NACs5.2 Non-Resettable Power ApplicationThe 5495 provides a dedicated 3

Seite 23 - Temporal-Coded Outputs

151161 iContentsSection 1Introduction ...

Seite 24

Model 5495 Distributed Power Module Installation Manual26 1511615.3 Door Holder ApplicationIn a typical door holder application, the door holder power

Seite 25 - 151161 21

Troubleshooting151161 27Section 6TroubleshootingLight-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.6.1 LEDs

Seite 26 - 22 151161

Model 5495 Distributed Power Module Installation Manual28 1511616.2 Trouble ConditionsNote: While Input 1 & 2 are activated, Input 1 & 2 will

Seite 27 - Sample Applications

Troubleshooting151161 296.3 Earth Fault ResistanceTable 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.Table

Seite 28 - 24 151161

Model 5495 Distributed Power Module Installation Manual30 1511616.4 Removing and Replacing the Control PanelThis section provides instruction on how t

Seite 29 - 151161 25

151161 31Appendix AUL Listed Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on ea

Seite 30 - 5.3 Door Holder Application

Model 5495 Distributed Power Module Installation Manual32 151161Faraday446 Vibrating Bell 476 Vibrating Bell477 Single Stroke Bell2700 -M. -R, -T, -Y,

Seite 31 - Troubleshooting

UL Listed Notification Appliances151161 33Faraday(cont.)5510 Strobe5511 Strobe5512 Strobe5516 Strobe5517 Strobe5518 Strobe5519 Strobe5521 4” Square Sy

Seite 32 - 6.2 Trouble Conditions

Model 5495 Distributed Power Module Installation Manual34 151161FCIS2415-FC StrobeS241575-FC StrobeS2430-FC Strobe130-3117C Mini Horn130-3147C Mini Ho

Seite 33 - 6.3 Earth Fault Resistance

UL Listed Notification Appliances151161 35FCIP2430W-FC Horn/StrobeP2430K-FC Horn/StrobeP2475-FC Horn/StrobeP2475W-FC Horn/StrobeP2475K-FC Horn/StrobeP

Seite 34

Model 5495 Distributed Power Module Installation Manualii 1511614.8.4 Setting the Auxiliary Output ...

Seite 35 - Appendix A

Model 5495 Distributed Power Module Installation Manual36 151161GentexGEC-24-15xxHorn/StrobeGEC-24-30xxHorn/StrobeGEC-24-60xxHorn/StrobeGEC-24-75xxHor

Seite 36 - 32 151161

UL Listed Notification Appliances151161 37Gentex(cont.)GES24-177xStrobeGES3-24xMulti Candella StrobeGESR-24xMulti Candella StrobeGEH-24xHornST24-30xSt

Seite 37 - 151161 33

Model 5495 Distributed Power Module Installation Manual38 151161System SensorCHRxChimeCHWxChimeCHSRxx2-Wire Chime/StrobeCHSWxx2-Wire Chime/StrobeHRxxH

Seite 38 - 34 151161

UL Listed Notification Appliances151161 39System Sensor(cont.)PC4Wxx4-Wire Horn/StrobeP4WHxx4-Wire Horn/Strobe High CandelaPC4WHxx4-Wire Horn/Strobe H

Seite 39

Model 5495 Distributed Power Module Installation Manual40 151161WheelockAH-12xHornAH-24xHornAH-12WPxHorn WeatherproofAH-24WPxHorn WeatherproofAMT-2415

Seite 40 - 36 151161

UL Listed Notification Appliances151161 41Wheelock(cont.)CH90-24MCCHxChime/StrobeHS-24xHornHS4-241575WxxHorn/StrobeHS4-24MCWxxHorn/StrobeHS4-24MCWHxxH

Seite 41 - 151161 37

Model 5495 Distributed Power Module Installation Manual42 151161Wheelock (cont.)RSS-121575WxStrobeRSS-241575WxStrobeRSS-24MCCxStrobeRSS-24MCCRxStrobeR

Seite 42 - 38 151161

UL Listed Notification Appliances151161 43Wheelock(cont.)RSSWP-24MCWHxStrobe Weatherproof ZRS-MCWHxStrobeZRS-24MCCxStrobeZRS-24MCCHxStrobeMB-G6-24 Mot

Seite 43

Model 5495 Distributed Power Module Installation Manual44 151161

Seite 44 - Wheelock

-1 151460Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a

Seite 45 - 151161 41

151161 1Section 1IntroductionThe 5495 is a notification appliance circuit and auxiliary power expander that provides up to 6 amps of filtered, 24 volt

Seite 46 - 42 151161

-212 Clintonville RoadNorthford, CT 06472USARA Number:___________________Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. S

Seite 48 - 44 151161

Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com

Seite 49 - Advanced Replacement Policy

Model 5495 Distributed Power Module Installation Manual2 151161Section 2UL RequirementsWhen installed in accordance with NFPA 70 and NFPA 72 standards

Seite 50 - Warn-HL-08-2009.fm

System Overview151161 3Section 3System Overview3.1 Terminal Descriptions and Electrical RatingsCAUTIONEach output circuit is rated at 3 amps. DO NOT

Seite 51

Model 5495 Distributed Power Module Installation Manual4 1511613.2 Signal Input TerminalsTerminals 14 through 19 are polarized signal input terminals.

Seite 52

System Overview151161 53.3 Notification Appliance Circuit TerminalsTerminals 3 through 10 are the notification appliance circuit output terminals. Eac